7.11 Pre Heating Info
This menu shows information about the system, enabled
CZ
zones and the controller (when the operating mode is
set to Pre Heating in the startup wizard).
DE
Menu tree*
Pre Heating Info
DK
EE
ES
*
Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
FI
s
ystem information
The system information menu shows the current time
FR
and date.
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
9 8
System information
Zone 1 Information
Zone 2 Information
Zone 3 Information
Zone 4 Information
Controller Information
z
1 i
one
nformation
This menu shows information about zone 1.
Menu tree
Zone 1 Information
Supply temperature
The current supply temperature is shown. The
temperature is measured by the supply temperature
sensor wired to the controller.
State
The current pre-heating state (phase) in the zone is
shown.
Pre heating is run in three different phases.
Pase 1: The supply temperature setpoint is set to
25 ˚C for 3 days (can be set in the Settings menu).
Pase 2: The supply temperature setpoint is set to
maximum allowed calculated setpoint for 4 days
(can be set in the Settings menu).
Pase 3: The controller enters Standby mode until
the startup wizard is restarted (Settings > Installer
Settings > Restart wizard). Frost protection is
active during this final phase.
Time Left
The time left of the current pre-heating phase in the
zone is shown.
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
Supply temperature
State
Time Left
Need help?