Mixing Valve
This menu enables access to mixing valve settings in the
zone.
MENU TREE
Mixing Valve
P-area
I-time
Actuator running time
P-AREA
In this menu the P-area for the mixing valve regulation
is set.
To set the P-area:
1. Select P-area.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 200.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
4. Confirm the setting by pressing the navigation
wheel again.
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
I-TIME
In this menu the I-time for the mixing valve regulation
is set.
To set the I-time:
1. Select I-time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 50 seconds
Setting range: 5 – 300 seconds, 1 second increments
4. Confirm the setting by pressing the navigation
wheel again.
ACTUATOR RUNNING TIME
In this menu the actuator running time for the mixing
valve regulation is set.
To set the actuator running time:
1. Select Actuator running time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 60 seconds
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation
wheel again.