EN
Mixing Valve
This menu enables access to mixing valve settings in the
CZ
zone.
MENU TREE
DE
Mixing Valve
DK
EE
P-AREA
In this menu the P-area for the mixing valve regulation
ES
is set.
To set the P-area:
FI
1. Select P-area.
2. Press the navigation wheel to confirm selection.
3. Set the value.
FR
Default: 140.0 ˚C
Setting range: 2.0 – 500.0 ˚C, 0.1 ˚C increments
HR
4. Confirm the setting by pressing the navigation
wheel again.
HU
I-TIME
In this menu the I-time for the mixing valve regulation
is set.
IT
To set the I-time:
1. Select I-time.
LT
2. Press the navigation wheel to confirm selection.
3. Set the value.
LV
Default: 35 seconds
Setting range: 5 – 300 seconds, 1 second increments
NL
4. Confirm the setting by pressing the navigation
wheel again.
NO
PL
PT
RO
RU
SE
SK
5 4
P-area
I-time
Actuator running time
ACTUATOR RUNNING TIME
In this menu the actuator running time for the mixing
valve regulation is set.
To set the actuator running time:
1. Select Actuator running time.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 120 seconds
Setting range: 0 – 500 seconds, 1 second increments
4. Confirm the setting by pressing the navigation
wheel again.
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
Need help?