Troubleshooting..............29 No communication between controller and BMS....29 Slow communication, or high latency, between Uponor system and BMS..............29 Wrong parameters changed in Uponor system compared to BMS settings............ 29 Uponor Smatrix Base PRO Controller X-148 Modbus RTU Installation manual...
U_BMS.txt • Floor temperature file match the Modbus RTU settings in the BMS. • Humidity level To connect a BMS to the Uponor Smatrix Base PRO controller some • Actuator status preparations must be made. • Pump or boiler status Connect and register thermostats and system device •...
Connect the controllers to each other using the Base PRO controller system device bus. X-148 SI0000223 The illustrations above show how to connect a BMS to the Modbus RTU interface on the controller. Uponor Smatrix Base PRO Controller X-148 Modbus RTU Installation manual...
T-144 Caution! T-145 T-146 Be thorough about the cabling and connections. T-148 Only use Uponor recommended cables and go for a line T-149 bus topology. SD0000033 Caution! Be prepared to add 120 ohm termination resistors between “A” and “B” on end devices, if the total bus length goes over 250 m or if any communication problems are noticed.
If no data value is availabe the celcius value is set to 0x0014 1802.6. 0x0019 The Uponor Smatrix Base PRO controller uses Fahrenheit (default) 0x001E to read and calculate temperatures. The temperature format can be 0x0023 changed in the U_BMS.txt file.
0x7FFF is returned if no data is available for the channel. These datapoints can be both read or written, and contain temperature setpoint and max/min temperature limits for each channel (1 to 12) on the controller. Uponor Smatrix Base PRO Controller X-148 Modbus RTU Installation manual...
Page 23
5 °C (41 °F). Room setpoint max 40015 40014 0x06 Write Analogue Signed 16 bit integer. temperature, channel 2 0x10 Write Range: min temperature - 35, multiple default: 35 °C (95 °F). Uponor Smatrix Base PRO Controller X-148 Modbus RTU Installation manual...
Page 24
35 °C (95 °F). Room setpoint min 40032 40031 0x06 Write Analogue Signed 16 bit integer. temperature, channel 10 0x10 Write Range: 5 - max temperature, multiple default: 5 °C (41 °F). Uponor Smatrix Base PRO Controller X-148 Modbus RTU Installation manual...
Page 25
Room floor max limit 40049 40048 0x06 Write Analogue Signed 16 bit integer. temperature, channel 7 0x10 Write Range: min temperature or 20 - 35, multiple default: 26 °C (78.8 °F). Uponor Smatrix Base PRO Controller X-148 Modbus RTU Installation manual...
4 Troubleshooting In case of problems and alarms in the Uponor Smatrix Base PRO system, check the table below. Otherwise see Uponor Smatrix Base PRO installation and operation manual section 16 for more information. 4.1 No communication between controller and BMS...
Page 30
Uponor Smatrix Base PRO Controller X-148 Modbus RTU Installation manual...
Page 31
Uponor Smatrix Base PRO Controller X-148 Modbus RTU Installation manual...
Page 32
Uponor GmbH Industriestraße 56, D-97437 Hassfurt, Germany Uponor reserves the right to make changes, without prior notification, 1090255 v4_11_2020_EN to the specification of incorporated components in line with its policy of www.uponor.com Production: Uponor/ELO continuous improvement and development.