Uponor Smatrix Base PRO Controller X-147
Modbus RTU interface
EN
Installation manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Smatrix Base PRO X-147 and is the answer not in the manual?

Questions and answers

Summary of Contents for Uponor Smatrix Base PRO X-147

  • Page 1 Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
  • Page 2: Table Of Contents

    Cooling not allowed for a room • Comfort setting • Integrated heat pump defrost state* Requires Heat Pump Integration via BMS to be activated in U_BMS.txt. Preparation # ... 2 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 3 That is, addressing multiple channels in one message. See Uponor Smatrix Base PRO installation and operation manual, or quick guide, for information registering devices to the controller. Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 3...
  • Page 4: Connecting The Bms Cable

    - connection on the Base PRO controller might be needed. 3. Connect power to the controller again. See documentation from BMS supplier for more information about BMS integration. 4 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 5: Installation Example, Beckhoff Modbus Rtu

    Caution! Depending of EMC conditions in the installation, and/or distance between the devices, the - connection on the Base PRO controller might be needed. Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 5...
  • Page 6: Supported Modbus-Rtu Functions

    Response example: Read Heating/Cooling and Comfort/ECO states Slave address Function code Byte count Coil status (0x01) (0x01) (0x01) 1 to 8 (0x02) 1 byte 1 byte 1 byte 1 byte 2 bytes 6 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 7: Frame Format: Read Discrete Input

    Coil status 1 to 8 Coil status 9 to 12 (0x01) (0x02) (0x02) (0xAA) (0x0A) 1 byte 1 byte 2 byte 1 bytes 1 bytes 2 bytes Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 7...
  • Page 8: Frame Format: Read Holding Registers

    Function code Byte count Holding register HI Holding register LO (0x01) (0x03) (0x02) (0x02) (0xBA) 1 byte 1 byte 1 byte 1 bytes 1 bytes 2 bytes 8 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 9 Byte count Holding register HI Holding register LO (0x01) (0x03) (0x02) (0x00) 2 °C (0x24) 1 byte 1 byte 1 byte 1 bytes 1 bytes 2 bytes Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 9...
  • Page 10: Frame Format: Read Input Registers

    (channel 12) (channel 12) (0x01) (0x04) (0x18) (0x02) (0xBA) (0x02) (0xBA) 1 byte 1 byte 1 byte 1 bytes 1 bytes 1 bytes 1 bytes 2 bytes 10 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 11 Function code Byte count Input register HI Input register LO (0x01) (0x04) (0x02) (0x00) (0xF6) 1 byte 1 byte 1 byte 1 bytes 1 bytes 2 bytes Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 11...
  • Page 12: Frame Format: Write Single Coil

    HI write LO (0x01) (0x05) (0x00) Register 2 (0x01) (0x00) (0x00) 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes 12 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 13: Frame Format: Write Single Holding Register

    HI write LO (0x01) (0x06) (0x00) Start at 59 (0x3A) (0x03) (0x02) 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 13...
  • Page 14 HI write LO (0x01) (0x06) (0x00) Start at 73 (0x48) (0x00) (0x5A) 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes 14 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 15: Frame Format: Write Multiple Coils

    Quantity of outputs address HI address LO (0x01) (0x0F) (0x00) (0x00) (0x00) (0x02) 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 15...
  • Page 16: Frame Format: Write Multiple Holding Registers

    HI written LO (0x01) (0x10) (0x00) Start at 21 (0x14) (0x00) (0x02) 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes 16 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 17: Available Variables

    18.0 64.4 0x284 0x0055 20.0 68.0 0x2A8 0x005A 21.0 69.8 0x2BA 0x005F 25.0 77.0 0x302 0x0064 30.0 86.0 0x35C 35.0 95.0 0x3B6 40.0 104.0 1040 0x410 Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 17...
  • Page 18: Controller Limitations

    It will shorten the heat up time for the room, which is useful in rooms where other heating sources, e.g. a fireplace, is present. When the BMS reads the comfort setting it will recieve the actual percentage. 18 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 19: Coil Data Points

    Write multiple 0x01 Read Unsigned. Cooling not allowed channel 9 00012 0x05 Write Binary 0 = Cooling not allowed 1 = Cooling allowed (default) 0x0F Write multiple Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 19...
  • Page 20 Requires Heat Pump Integration via BMS to be activated in U_BMS.txt. It takes about 2 minutes for the actuators in the Base PRO system to be fully opened. 20 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 21: Discrete Input Data Points

    Read Binary Unsigned. 1 = ON, 0 = Off. GPI status (bit 13) 10014 0x02 Read Binary Unsigned. 1 = ON, 0 = Off. 10015 10016 Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 21...
  • Page 22: Input Register Data Points

    Humidity data channel 11 30024 0x04 Read Analogue 0-100 % relative humidity Unsigned 16 bit integer. Humidity data channel 12 30025 0x04 Read Analogue 0-100 % relative humidity 22 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 23: Floor Temperature

    +1 = 0001 integrated heat pump 0 = 0000 -1 = 00FF -10 = 00F6 Requires Heat Pump Integration via BMS to be activated in U_BMS.txt. Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 23...
  • Page 24 Read Signed 16 bit integer. Room setpoint temperature channel 40012 0x06 Write Analogue Range: min - max temperature, default: 21 °C (69.8 °F). 0x10 Write multiple 24 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 25 Write Signed 16 bit integer. Room setpoint min temperature 40032 Analogue Range: 5 - max temperature, channel 10 0x10 Write multiple default: 5 °C (41 °F). Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 25...
  • Page 26 Signed 16 bit integer. Room floor min limit temperature 40052 Analogue Range: 10 - 30 or max temperature, channel 8 0x10 Write multiple default: 20 °C (68 °F). 26 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 27 Signed 16 bit integer. Comfort setting channel 10 40070 0x06 Write Analogue Range: 0 = off, 5 - 12 = 5 - 12 % default: 0. 0x10 Write multiple Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 27...
  • Page 28 0x03 Read Signed 16 bit integer. Heating/cooling offset temperature 40073 0x06 Write Analogue Range: 0 - 5 °C default: 2 °C (2 °F). 0x10 Write multiple 28 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
  • Page 29 Wrong parameters are changed in the registered in the system changed in Uponor system Uponor system after new values are sent compared to BMS settings from the BMS Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 29...
  • Page 30 Uponor GmbH Industriestraße 56, D-97437 Hassfurt, Germany Uponor reserves the right to make changes, without prior notification, 1090255 03_2018 to the specification of incorporated components in line with its policy Production: Uponor / MRY www.uponor.com of continuous improvement and development.