Cooling not allowed for a room • Comfort setting • Integrated heat pump defrost state* Requires Heat Pump Integration via BMS to be activated in U_BMS.txt. Preparation # ... 2 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
Page 3
That is, addressing multiple channels in one message. See Uponor Smatrix Base PRO installation and operation manual, or quick guide, for information registering devices to the controller. Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 3...
- connection on the Base PRO controller might be needed. 3. Connect power to the controller again. See documentation from BMS supplier for more information about BMS integration. 4 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
Caution! Depending of EMC conditions in the installation, and/or distance between the devices, the - connection on the Base PRO controller might be needed. Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 5...
HI written LO (0x01) (0x10) (0x00) Start at 21 (0x14) (0x00) (0x02) 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 2 bytes 16 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
It will shorten the heat up time for the room, which is useful in rooms where other heating sources, e.g. a fireplace, is present. When the BMS reads the comfort setting it will recieve the actual percentage. 18 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
Write multiple 0x01 Read Unsigned. Cooling not allowed channel 9 00012 0x05 Write Binary 0 = Cooling not allowed 1 = Cooling allowed (default) 0x0F Write multiple Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 19...
Page 20
Requires Heat Pump Integration via BMS to be activated in U_BMS.txt. It takes about 2 minutes for the actuators in the Base PRO system to be fully opened. 20 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
+1 = 0001 integrated heat pump 0 = 0000 -1 = 00FF -10 = 00F6 Requires Heat Pump Integration via BMS to be activated in U_BMS.txt. Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 23...
Page 24
Read Signed 16 bit integer. Room setpoint temperature channel 40012 0x06 Write Analogue Range: min - max temperature, default: 21 °C (69.8 °F). 0x10 Write multiple 24 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
Page 25
Write Signed 16 bit integer. Room setpoint min temperature 40032 Analogue Range: 5 - max temperature, channel 10 0x10 Write multiple default: 5 °C (41 °F). Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 25...
Page 26
Signed 16 bit integer. Room floor min limit temperature 40052 Analogue Range: 10 - 30 or max temperature, channel 8 0x10 Write multiple default: 20 °C (68 °F). 26 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
Page 27
Signed 16 bit integer. Comfort setting channel 10 40070 0x06 Write Analogue Range: 0 = off, 5 - 12 = 5 - 12 % default: 0. 0x10 Write multiple Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 27...
Page 28
0x03 Read Signed 16 bit integer. Heating/cooling offset temperature 40073 0x06 Write Analogue Range: 0 - 5 °C default: 2 °C (2 °F). 0x10 Write multiple 28 l Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual...
Page 29
Wrong parameters are changed in the registered in the system changed in Uponor system Uponor system after new values are sent compared to BMS settings from the BMS Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface l Installation manual l 29...
Page 30
Uponor GmbH Industriestraße 56, D-97437 Hassfurt, Germany Uponor reserves the right to make changes, without prior notification, 1090255 03_2018 to the specification of incorporated components in line with its policy Production: Uponor / MRY www.uponor.com of continuous improvement and development.