MIN. SUPPLY TEMP. (IDLE STATUS)
In this menu the minimum available supply temperature
CZ
for the zone, while meltaway status is IDLE, can be set.
The supply temperature is not allowed to fall below this
value.
DE
This menu is only shown if Zone Setup is set to
Meltaway for the zone.
DK
To set the minimum available supply temperature:
1. Select Min. supply temp.
EE
2. Press the navigation wheel to confirm selection.
3. Set the value.
ES
Default: 5.0 ˚C
Setting range: 0.0 – 25.0 ˚C, 0.1 ˚C increments
FI
4. Confirm the new setting by pressing the navigation
wheel again.
MAX. SUPPLY TEMP. (IDLE STATUS)
FR
In this menu the maximum available supply temperature
for the zone, while meltaway status is IDLE, can be set.
HR
The supply temperature is not allowed to rise above this
value.
This menu is only shown if Zone Setup is set to
HU
Meltaway for the zone.
To set the minimum available supply temperature:
IT
1. Select Max. supply temp.
2. Press the navigation wheel to confirm selection.
LT
3. Set the value.
Default: 15.0 ˚C
Setting range: 0.0 – 70.0 ˚C, 0.1 ˚C increments
LV
4. Confirm the new setting by pressing the navigation
wheel again.
NL
NO
PL
PT
RO
RU
SE
SK
7 0
DEVIATION ALARM LIMIT
In this menu the deviation alarm limit for the supply
temperature in the zone is set. If the difference between
the measured and the calculated supply temperatures
are higher than the set limit during the time set in
Deviation alarm delay, the alarm is triggered.
To set the deviation alarm limit:
1. Select Deviation alarm limit.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 10.0 ˚C
Setting range: 0.0 – 50.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
DEVIATION ALARM DELAY
In this menu the deviation alarm delay for the deviation
alarm limit in the zone is set. If the difference between
the measured and the calculated supply temperatures
are higher than Deviation alarm limit during the set
delay, the alarm is triggered.
To set the deviation alarm delay:
1. Select Deviation alarm delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 5 min
Setting range: 0 – 30 min, 1 min increments
4. Confirm the new setting by pressing the navigation
wheel again.