No communication between controller and BMS....30 Slow communication, or high latency, between Uponor system and BMS..............30 Wrong parameters changed in Uponor system compared to BMS settings............ 30 Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
* Requires Heat Pump Integration via BMS to be activated in U_BMS.txt. Slave 1 U_BMS.txt Slave 2 U_BMS.txt # ... Slave ... U_BMS.txt SI0000218 Slave 1 Slave 2 Slave ... SI0000219 Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
Page 4
247, unique for each controller in the system), and that the other setting match the Modbus RTU settings in the BMS. To connect a BMS to the Uponor Smatrix Base PRO controller some preparations must be made. Connect and register thermostats, and system devices, to the controllers.
Caution! Depending of EMC conditions in the installation, and/or distance between the devices, the - connection on the Base PRO controller might be needed. Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
(without the ECO setback value applied). 0x5A Example Setpoint written/read from BMS 21 ˚C (69.8 °F) Comfort/ECO state 1 (ECO) Setpoint shown in thermostat 17 ˚C (62.6 °F) Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
0x7FFF is returned if no data is available for the channel. These datapoints are read only and show the current sensor value (temperature or humidity) for each channel (1 to 12) on the controller. Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
Page 22
2 Floor temperature data, 30028 30027 0x04 Read Analogue Signed 16 bit integer. channel 3 Floor temperature data, 30029 30028 0x04 Read Analogue Signed 16 bit integer. channel 4 Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
0x06 Write Range: min - max temperature, 0x10 Write default: 21 °C (69.8 °F). multiple Room setpoint temperature, 40005 40004 0x03 Read Analogue Signed 16 bit integer. channel 5 Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
Page 24
35 °C (95 °F). Room setpoint min 40020 40019 0x06 Write Analogue Signed 16 bit integer. temperature, channel 4 0x10 Write Range: 5 - max temperature, multiple default: 5 °C (41 °F). Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
Page 25
Room floor max limit 40037 40036 0x06 Write Analogue Signed 16 bit integer. temperature, channel 1 0x10 Write Range: min temperature or 20 - 35, multiple default: 26 °C (78.8 °F). Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
Page 26
Room floor min limit 40054 40053 0x06 Write Analogue Signed 16 bit integer. temperature, channel 9 0x10 Write Range: 10 - 30 or max temperature, multiple default: 20 °C (68 °F). Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
4 Troubleshooting In case of problems and alarms in the Uponor Smatrix Base PRO system, check the table below. Otherwise see Uponor Smatrix Base PRO installation and operation manual section 16 for more information. 4.1 No communication between controller and BMS...
Page 31
Uponor Smatrix Base PRO Controller X-147 Modbus RTU interface Installation manual...
Page 32
Uponor GmbH Industriestraße 56, D-97437 Hassfurt, Germany Uponor reserves the right to make changes, without prior notification, 1090255 v3_07_2020_EN to the specification of incorporated components in line with its policy of www.uponor.com Production: Uponor/MRY continuous improvement and development.