Uponor Smatrix Move PRO Installation And Operation Manual page 49

Hide thumbs Also See for Smatrix Move PRO:
Table of Contents

Advertisement

MIN. SUPPLY TEMP.
In this menu the minimum allowed supply temperature
for the zone can be set. The supply temperature is not
allowed to fall below this value.
To set the minimum allowed supply temperature:
1. Select Min. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 15.0 ˚C
Setting range: 5.0 – 35.0 ˚C (or max. supply temp), 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation
wheel again.
MAX. SUPPLY TEMP.
In this menu the maximum allowed supply temperature
for the zone can be set. The supply temperature is not
allowed to rise above this value.
To set the maximum allowed supply temperature:
1. Select Max. supply temp.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 70.0 ˚C
Setting range: 5.0 (or min. supply temp) – 90.0 ˚C, 0.1 ˚C
increments
4. Confirm the new setting by pressing the navigation
wheel again.
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
DEVIATION ALARM LIMIT
In this menu the deviation alarm limit for the supply
temperature in the zone is set. If the difference between
the measured and the calculated supply temperatures
are higher than the set limit during the time set in
Deviation alarm delay, the alarm is triggered.
To set the deviation alarm limit:
1. Select Deviation alarm limit.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 10.0 ˚C
Setting range: 0.0 – 50.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
DEVIATION ALARM DELAY
In this menu the deviation alarm delay for the deviation
alarm limit in the zone is set. If the difference between
the measured and the calculated supply temperatures
are higher than Deviation alarm limit during the set
delay, the alarm is triggered.
To set the deviation alarm delay:
1. Select Deviation alarm delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 5 min
Setting range: 0 – 30 min, 1 min increments
4. Confirm the new setting by pressing the navigation
wheel again.
EN
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
4 9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Smatrix Move PRO and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents