DEVIATION ALARM LIMIT
In this menu the deviation alarm limit for the supply
temperature in the zone is set. If the difference between
the measured and the calculated supply temperatures
are higher than the set limit during the time set in
Deviation alarm delay, the alarm is triggered.
To set the deviation alarm limit:
1. Select Deviation alarm limit.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Stand Alone Control/Smatrix Base PRO:
Default: 10.0 ˚C
Setting range: 0.0 – 50.0 ˚C, 0.1 ˚C increments
Domestic Hot Water:
Default: 10 ˚C
Setting range: 0.0 – 30.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
DEVIATION ALARM DELAY
In this menu the deviation alarm delay for the deviation
alarm limit in the zone is set. If the difference between
the measured and the calculated supply temperatures
are higher than Deviation alarm limit during the set
delay, the alarm is triggered.
To set the deviation alarm delay:
1. Select Deviation alarm delay.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Stand Alone Control/Smatrix Base PRO:
Default: 5 min
Setting range: 0 – 30 min, 1 min increments
Domestic Hot Water:
Default: 60 seconds
Setting range: 0 – 600 seconds, 1 second increments
4. Confirm the new setting by pressing the navigation
wheel again.
U P O N O R S M AT R I X M O V E P R O · I N S TA L L AT I O N A N D O P E R AT I O N M A N U A L
Indoor Temp. Settings
This menu enables access to settings related to the
room temperature sensor in the zone.
This menu and its submenus are only shown if Heating
Mode is set to Outdoor + Indoor comp..
MENU TREE*
Indoor Temp. Settings
Indoor Setpoint
Calculated Indoor Setpoint
ECO-Comf. Status
Indoor Setpoint Influence
(Lower)
Indoor Setpoint Influence
(UPPER)
*
Parts of the menu tree may only be visible in the Move PRO
controller depending on its current configuration.
INDOOR SETPOINT
In this menu the indoor temperature setpoint for the
zone is set.
This information is only shown if Zone Setup is set to
Stand Alone Control for the zone.
To set the indoor temperature setpoint:
1. Select Indoor Setpoint.
2. Press the navigation wheel to confirm selection.
3. Set the value.
Default: 21.0 ˚C
Setting range: 5.0 – 35.0 ˚C, 0.1 ˚C increments
4. Confirm the new setting by pressing the navigation
wheel again.
EN
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
5 9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Smatrix Move PRO and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents