<Reset>
Sensor Adjustment
166
Manual Off
To change the control status of a single relay output, simply place the cursor on the
status (Auto, Manual On, or Manual Off), toggle with the +/- key, use the arrow keys
to change the field, and then press ENTER.
In the center at the bottom of the screen is a <Reset> field. If you place the cursor
on this field and press ENTER, all relay outputs will be reset to Auto (SC 255 con-
trol).
Select Sensor Adjustment from the Suction Service menu, and this screen appears:
ach sensor's current reading appears next to its name. There are three additional
E
columns:
Man
AK2-SC 255 Reference Manual
until reset.
The relay output is in override and will remain OFF
until reset.
(List box: M, blank) This field allows you to set a the