ClimaTECH
heating configuration
102
Unoccupied setpoint
Lockout below ambient
Delay between stages
There are two pages of settings for heating configuration:
Num of heat rclm stages
Occupied setpoint
Unoccupied setpoint
Lockout above ambient
Delay between stages
Heat reclaim flush start
Flush duration
Number of aux heat stages (0 to 4) The number of configured auxiliary heat
Occupied setpoint
Unoccupied setpoint
AK2-SC 255 Reference Manual
hours as configured in the Store Info screen.
(0.0 to 150.0) The cooling setpoint during store closed
hours as configured in the Store Info screen.
(0.0 to 150.0) The outside ambient temperature below
which cooling will be locked out.
(0 to 99) The number of minutes after the start of a
cooling stage before the next stage can start. Also, the
minimum on time for every stage.
(0 to 4) The number of heat reclaim stages.
(0.0 to 150.0) The heat reclaim setpoint during operat-
ing hours as configured in the Store Info screen.
(0.0 to 150.0) The heat reclaim setpoint during store
closed hours as configured in the Store Info screen.
(0.0 to 150.0) The outside ambient temperature above
which heat reclaim will be locked out.
(0 to 99) The number of minutes after the start of a
heat reclaim stage before the next stage can start.
Also, the minimum on time for every stage.
(Time of day field) The time for heat reclaim flush to
begin each day.
(0 to 99) The number of minutes' duration for each
heat reclaim flush.
stages in the HVAC unit.
(0.0 to 150.0) The zone temperature setpoint for
auxiliary heat during operating hours as configured in
the Store Info screen.
(0.0 to 150.0) The zone temperature setpoint for
auxiliary heat during store closed hours as configured
in the Store Info screen.