Compressor Oil And Safety Information - Danfoss AK2-SC 255 Reference Manual

Rack controller
Hide thumbs Also See for AK2-SC 255:
Table of Contents

Advertisement

Configuring other
compressors in the
suction group
Compressor oil and
safety information
22
Paging down, you will find a page for each compressor in the suction group. These
subsequent screens will have only questions pertaining to the individual compressors,
not the rack questions found at the top of the screen for compressor number one.
After basic operating data has been entered for all compressors, paging down will
produce this screen:
The fields and their contents are as follows:
Oil control
Type of oil monitor
Lockout comp on oil fail
Low oil pressure diff
Oil pressure delay
No of oil reset attempts
Min time between resets
Monitor comp disch temp (List box: Yes, No) Whether or not compressor
AK2-SC 255 Reference Manual
(List box: Yes, No) Whether or not oil control is
implemented.
(List box:)
Sensor Input: An analog input (sensor input) is used
to monitor oil pressure.
On/Off: A digital input (on-off input) is used to monitor
an oil pressure switch.
Copeland: A Copeland oil monitor is used.
(List box: Yes, No) Whether or not compressors will
be locked out when an oil failure is detected.
(0 to 50) The oil pressure differential, when an analog
sensor input is used, that will cause compressor
shutdown.
(0 to 255) When an analog sensor is used, the number
of seconds after oil failure is detected before compres-
sors are reset.
(0 to 10) After oil failure is detected, the number of
reset attempts before compressors are locked out.
(0 to 60) After a reset (whether successful or not) the
number of minutes that must elapse before another
reset attempt.
discharge temperature is monitored.
RS.8D.M1.22