Configuring RTC I/O
variable outputs
92
AK2-SC 2 55 Bd-Pt
In the lower half of the screen, the SC 255 Inputs:
Name
Bcast
On
Bd-Pt
Here is the screen for variable (analog) outputs, reached with the fourth icon from
left. The names appear if the points are configured.
AK2-SC 255 Reference Manual
changed.
No: The input is not configured. Its state can not be
used by the controller.
Rec: The input value is to be received from another
node (other than this RTC board) on the I/O network.
The board and point that is broadcasting the state of
the input must be given in the next column.
(Address field) If the input state is received from
another node on the I/O network, enter here the
address of the point that is to be received.
(Label field, not changeable) The name of the point.
The RTC board's software can only use the listed
inputs from the I/O network. The names always
appear as in the illustration above, whether the input is
used or not.
(List field, one for each point:)
No: The input is not configured or its state is not to be
used by the controller.
Rec: The input value is to be received from another
node (other than this RTC board) on the I/O network.
The board and point that is broadcasting the state of
the input must be given in the next column.
(List field:)
Voltage: The input state will read ON when the point
senses voltage.
No Voltage: The input state will read ON when the
point senses no voltage.
(Address field) If the input state is received from
another node on the I/O network, enter here the
address of the point that is to be received.
RS.8D.M1.22