Board & Points Configuration, Lighting - Danfoss AK2-SC 255 Reference Manual

Rack controller
Hide thumbs Also See for AK2-SC 255:
Table of Contents

Advertisement

Board & points
configuration
(lighting)
Powerlink
configuration
Cutler-Hammer
configuration
RS.8D.M1.22
Minimum ON time
Minimum OFF time
Enable dimmer output
Target
Minimum output
Reaction time
Override switch
Override duration
Burglar override
Pre delay
Fire override
Lighting schedules are found on the next page(s).
Board and points configuration must be completed for all types of points. Do this in
accordance with the appendix on board & point configuration.
Configuration of Powerlink lighting zones configuration is the same as for the SC 255
zones just discussed, except that the question Number of control relays is replaced
with Number of control points. These panels also require board and point setup and
initialization (see below).
Configuration of Powerlink lighting zones configuration is the same as for the SC 255
zones just discussed, except that the question Number of control relays is replaced
with Number of control points. These panels also require board and point setup and
initialization (see below).
AK2-SC 255 Reference Manual
will be turned off.
(0 to 255) When lights are turned on, the number of
minutes that they must remain on before being turned
off.
(0 to 255) When lights are turned off, the number of
minutes that they must remain off before being turned
on.
(List box: Yes, No) Whether or not a dimmer variable
output will be controlled.
(0 to 100) The photocell level that the controller will
seek to maintain by operation of the dimmer.
(0 to 100) The minimum dimmer level.
(List box: Slowest, Slow, Normal, Fast, Fastest) The
relative sensitivity of control to changes in photocell
level.
(List box: Yes, No) Whether or not there is an override
switch assigned to the zone.
(Time field: 00:00 to 23:59) The duration of an override
when the override switch is used.
(List box: Yes, No) When this zone's lights are turned
off, whether they are to be turned on when a moni-
tored burglar alarm is sensed.
(0 to 600) When this zone's lights are off and a burglar
override is called for, the number of minutes delay
before the zone is turned on.
(List box: Yes, No) When this zone's lights are turned
off, whether they are to be turned on when a moni-
tored fire alarm is sensed. There is no pre-delay for
fire alarms.