RTC dehumidification
configuration
86
Night setback offset
Minimum ON time
Minimum OFF time
There are two pages of dehumidification configuration settings:
Dehumidification type
Aux heat during dehumid
Control dehumid. on
Control dehumid. using
AK2-SC 255 Reference Manual
when the store is closed according to a schedule or
schedules configured in the Store Info screens.
(-50.0 to 50.0) The amount by which the heating
setpoint (set on previous page) is to be lowered during
non-scheduled hours (as set in the Store Info screens).
(0 to 60) The minimum number of minutes heating
must run after being turned on before being turned off.
(0 to 60) The minimum number of minutes heating
must remain off after being turned off before being
turned on.control actions. See preceding two settings.
(List box: None, Cooling) The type of dehumidification
used.
(List box: Yes, No) Whether or not auxiliary heat is
allowed during dehumidification.
(List box:)
Humidity: Dehumidification will be controlled based
on a specified humidity target. A humidity sensor is
required.
Calc Dewpt: Dehumidification will be controlled
based on a specified dewpoint target, which will be
compared with a dewpoint calculated from zone
temperatuare and humidity. Both zone temperature
and humidity sensors must be installed.
(List box, if controlled by dewpoint or humidity only,
and if there are multiple sensors:)
Average: Control will be based on the average of a
group of sensors.
High: The high value of a group of sensors will be
used.