SC4condenser
configuration
SC4 alarms
configuration
SC4 board & points
configuration
RS.8D.M1.22
Override switch
Override duration
Num of schedules
Seasons 4 password
Number of fans
Minimum run time
Liquid Temp Setpoint
Range
SC4 alarms are configured as are RTU alarms.
SC4 board & points are configured as are RTU board & points.
AK2-SC 255 Reference Manual
(List box: Yes, No) Whether or not there is an over-
ride switch wired to a digital input.
(0 to 1439) The number of minutes that control will be
overridden after operation of the override switch.
(0 to 8) The number of operating schedules entered
on the following page(s).
(5-character auth code) The password given by
Seasons 4 to the equipment owner.
(List box: None, Six, Eight) The number of HVAC
condenser fans controlled in this unit.
(0 to 60) The number of minutes that a stage must run
before being turned off.
(0.0 to 150.0, one setpoint per stage) The stage will be
turned on at setpoint plus range and turned off after
the stage above is turned off, at setpoint minus range.
(0.0 to 150.0, one setpoint per stage) The stage will be
turned on at setpoint plus range and turned off after the
stage above is turned off, at setpoint minus range.
99