RS.8D.M1.22
same screen with all its fields revealed appears as at right.
The fields are as follows:
Fixture Type
Fixture Name
Enter user defined name
Monitor box door
Shutdown when door open (List box: Yes, No) Whether or not to shut down
No case/box sensors
Temperature control
Controlling sensor
Target:
AK2-SC 255 Reference Manual
(List box) Various types of fixture can be selected:
box, multi-deck, single deck, service, etc.
(List box) There is a large selection of common fixture
names for each of the fixture types that can be se-
lected above, and there is a selection User Def. After
making that selection, you will be able to spell out your
own name on the following line.
(Label) The name of a user-defined fixture. Any of
the characters in the AK2-SC 255 character set can be
used, including upper and lower case letters and
symbols.
(List box: Yes, No) Whether or not a box door switch
will be monitored (appears for boxes only).
refrigeration when the box door is open.
(0 to 15) The number of sensors in this fixture or
circuit.
(List box: Yes, No) Whether or not temperature contol
will be used.
(List box:)
Min Temp The lowest of the sensors in the fixture or
on the circuit will be used for temperature control.
Max Temp The highest of the sensors in the fixture
or on the circuit will be used for temperature control.
Average The average of all the sensors in the fixture
or on the circuit will be used for temperature control.
[circuit names] The name of each sensor will be
listed, and any can be selected. That sensor, then, will
be used for temperature control.
(-99.0 to 150.0 [target] 1.0 to 20.0 [range] The target