Sensor Commissioning; Calibrating And Checking Probes; Cleaning And Servicing Probes - ProMinent Aegis-II Assembly And Operating Instructions Manual

Cooling tower and boiler controller
Hide thumbs Also See for Aegis-II:
Table of Contents

Advertisement

9.5.2 Sensor Commissioning

Before putting into operation, the protective
cap or case must be removed from the glass
or metal electrode. The glass or metal
electrode must be free from oil, grease and
other contaminations. Likewise, the diaphragm
of the reference electrode must be free from
scale deposits, dirt or crystallized matter. For
these reasons, electrodes should never be
touched by hand. If contaminations are present
refer to Chap. 4. "Cleaning and servicing".

9.5.3 Calibrating and checking probes

9.5.3.1 Calibrating pH probes
Zero calibration: since pH probes are subject
to certain manufacturing tolerances, they must
be tuned to the pertinent pH transmitter. The
adjustment intervals depend on relevant
operating conditions. They can vary from a few
days to up to 8 weeks.
Having connected the probe to the transmitter
by means of the probe cable (taking care that
connectors and cable remain absolutely dry),
dip the probe into a pH 7 standardizing
solution and adjust transmitter exactly to read
this value.
Remove the probe, rinse it with water,
preferably distilled water, and dry it by
swabbing it with soft, lint free tissue paper.
Immerse the probe in a buffer solution differing
by a least 2 pH from pH 7 and calibrate after
the value on the display has stabilized. If
within 30 seconds a steady-state value is not
produced or calibration has proved
impossible, clean probe as described in
Section 4 and repeat calibration. If again
unsuccessful, replace probe with a new one.
9.5.3.2 Checking redox/ORP probes
With the probe connected to the controller by
means of the probe cable (taking care that
connectors and cable remain absolutely dry),
dip the probe into a redox-ORP standard
solution, e.g. of 465 mV.
The reading should reach or exceed this value
within not more than 30 seconds. If the reading
rises rather sluggishly or falls short more than 20
mV, clean the probe as described in Section 4
and repeat check. If again unsuccessful, replace
the probe with a new one, or adjust the ORP set-
point accordingly.
NOTE
transmitter or ORP input driver card
will not normally be required. This
procedure serves as a probe check
only.

9.5.4 Cleaning and servicing probes

All pH and ORP probes should regularly (once a
month) undergo a visual check and be cleaned if
necessary.
If deposits on the glass electrode withstand
cleaning with a soft, moistened cloth, or a soft
toothbrush the following cleaning agents may be
used:
Kind of deposit
General deposits
Scale or metal
hydroxides
Oil, grease
Biofouling
Table 13 Glass electrode cleaning agents
It is essential that the probes are rinsed thoroughly
after cleaning or using a buffer solution.
If the laterally arranged ceramic diaphragm of the
reference electrode is blocked, it may be cleaned
like the glass electrode. In addition it may be
cleaned by cautious scraping with a finger nail, a
razor blade or a fine file, but care must be taken
that the diaphragm is not scratched.
Page 51 of 102
Programming the Inputs
A calibration of the
Agent and duration of
application
Non-abrasive
household cleaner like
®
®
Dawn
or 409
Diluted hydrochloric
acid (approx. 0.1-3 %,
1-5 minutes)
Solvents, like alcohol
Mixture of diluted
hydrochloric acid and
pepsin, several hours.
Solvents (e.g. acetone)
must not be used to
clean electrodes as
they can damage the
plastic