10.6.3 Feed Based on Bleed and/or Feed

The Aegis II has two feed modes based on how long
the bleed valve is open. The Feed relay in the Bleed
then Feed program will wait until the Bleed is
complete, then calculate how long to feed based on
the percentage selected.
Prior to configuring these program steps, you need
to enable a Blowdown relay.
Configuring a Blowdown
Relay.
enabled the Feed relay, see
Feed Relay
10.6.3.1 Bleed then Feed
1- Press MENU.
2- Scroll down to Set Feed Mode. Press OK
3- Scroll down to the relay you wish to use to
control the pump. Press OK.
4- Scroll down to the
Bleed then Feed
press OK.
5- Scroll down to the blowdown valve you will be
using and press the F1,
6- Press the F2,
SETPNT
7- Use the arrows to edit the % value per the
above explanation. Press OK to save.
A pulse relay will feed X milliliters per minute.
See section
9.4
If you have not
section
9.5 Configuring a
choice and
.
Select
key.
Page 69 of 102
Programming the Outputs
10.6.3.2 Bleed and Feed
The Aegis II has two feed modes based on how long
the bleed valve is open.
The Feed relay in the Bleed and Feed program is
based on a 5 minute time frame. The controller
calculates how long the feed pump should be on
based on 300 seconds X the percentage entered
and starts to feed when the remainder of the 300
second bleed equals this calculated amount.
Example: If the percent is 80, the controller
calculates 80% of 300 or 240 seconds, then starts
the feed when the bleed count down reaches 240
seconds. Both relays will count down to zero. The
feed relay will stop. The bleed will reset to 300
seconds and continue counting down.
When the bleed stops, the feed stops and the
counters are reset.
Prior to configuring these program steps, you need
to enable a Blowdown relay. See section
Configuring a Blowdown
enabled the Feed relay, see section
Configuring a Feed Relay
1- Press MENU.
2- Scroll down to Set Feed Mode. Press OK.
3- Scroll down to the relay you wish to use to
control the pump. Press OK.
4- Scroll down to the Bleed then Feed choice and
press OK.
5- Scroll down to the blowdown valve you will be
following and press the F1,
6- Press the F2,
Set-point
7- Use the arrows to edit the % value per the
above explanation. Press OK to save.
10.5
Relay. If you have not
10.6
key.