11.8 Configurations
See section
13.2.1 USB – Save or Load the
Program
12 Controller Technical Data:
12.1 Fuse Specification
The power relay fuse is 6.3 amps at 250 volts AC. This fuse is similar to the relay fuse used on the MultiFLEX and
Aegis, except this is a slow blow fuse. Do not use this fuse in those controllers.
However, you can use the fast blow fuses provided with those controllers in the Aegis II. A fast blow fuse will not
harm the device.
Component
Controller,
Complete
Controller,
Complete
Power relay
R1,R2 and Power
Out terminals
Main Power Fuse
Enclosure
Table 17 Fuse Specifications
Rating/type
100-230VAC, 50/60 Hz, 0.5-0.26A -
No External Load
100-230VAC, 50/60 Hz, 7.8A - with
External Load
6.3 AT @250VAC 5x20mm, Slow-
Blow, Glass Fuse
1.6AT 250VAC 5x20, 1.5 kA at 250
VAC ,Ceramic Fuse
Rated for IP65
Page 93 of 102
vendor
Part#
PFC
AGIb
PFC
AGIb
PFC
732379
PFC
732411
PFC
N/A
System Menu