System Menu; Communications; How To Change The Ip Address - ProMinent Aegis-II Assembly And Operating Instructions Manual

Cooling tower and boiler controller
Hide thumbs Also See for Aegis-II:
Table of Contents

Advertisement

System Menu

11 System Menu
The System Menu is accessed by pressing the
MENU key followed by the up arrow and the OK key.
The following sections discuss the options available
and how to edit the information. The options below
appear in the order they are in the display if you use
the down arrow to scroll.
The choices are:

Communications

System Setup
Time and Date
Set Sensor Type
Enable I/O
Passwords
Activity Log
Diagnostic
Configurations
11.1 Communications
The Communications section has the IP addresses
for the LAN and WiFi connections. Scroll down
through; LAN IP Address, WiFi Netmask Address,
WiFi IP Address, LAN Gateway, MAC Address and
LAN Netmask.
Address Type
LAN IP Address
WiFi Netmask
Address
WiFi IP Address
LAN Gateway
Mac Address
LAN Netmask
Table 15 IP Addresses
The LAN address and Netmask can be changed if
the controller will be on a network. The network
administrator must provide a LAN address for this
device. Edit them here.
WiFi is how to connect wirelessly. Enable WiFi on
your PC, Notebook or Smartphone.
The MAC address is assigned to the controller from
the factory and cannot be changed. It is unique in
the world.
Default Setting
10.10.6.106
255.255.255.0
192.168.1.1
192.168.100.1
nn.nn.nn.nn.nn.nn
255.255.255.0

11.1.1 How to Change the IP Address:

The factory default IP Address of the controller
is10.10.6.106.
You can connect any PC
device with an Ethernet port
to the controller using a CAT5
Ethernet cable.
Set up your device with a
static IP address of
10.10.6.nnn, where, 'nnn' is a
3 digit number from 000 to
255 but not 106. 106 is the
unique address of the
controller.
Open a browser and enter
10.10.6.106 into the search
box to make an HTTP
connection to the controller.
Refer to the Browser manual
for more details.
If your controller is attached
to a local area network (LAN)
the IP address of the
controller will need to be
changed to match the plant
scheme. This address is
assigned by the site IT staff.
Enter that address as shown
here.
1- To Edit IP Address press
MENU
2- Use Up/Down Arrows to
navigate to System then
press OK
3- Scroll to Communication
then press OK
4- Use F1 to go to Edit Mode
5- Use Up/Down and Left/Right Arrow keys to Edit
the IP Address then Press F1 to save the
change
6- Press NEXT to go to Netmask setting
7- Use F1 to go to Edit Mode if necessary
8- Use Up/Down and Left/Right Arrow keys to Edit
the Netmask then Press F1 to save the change
9- Use ESC key to exit and return to the main
display
Page 88 of 102