Programming the Outputs
choose to set the output to drop to 0%
(4mA) or remain as is when the keypad Stop
button is pressed. This allows you to shut
down the output to a pump, or continue to
send a value to a DCS.
10.16.4
How to set 4-20mA output to
Manual Mode:
1- To Set 4-20mA output to Manual press MENU
2- Use Up/Down Arrows to navigate to I/O Setup
3- Scroll to select the desire 4-20mA output (for
example E:4-20mA output) and press OK and
then press F3 to set it to Manual
4- Use Up/Down and Right/Left Arrow keys to set
the desire percentage (0-100% is 4-20mA),
press F1 and then F2
5- Press F2 to go to next display since we are not
controlling the output with any type of sensor in
Manual Mode
6- If any interlocked needed use UP/Down arrow
keys to select one of the digital or phantom
inputs then press F1 and then F2 to go to next
display
7- If any open loop alarm needed (if the 4-20mA
output doesn't see a closed loop you will get
open loop alarm) use F3 to switch back and
forth between ON and OFF and F1 to save
changes
8- Use ESC key to Exit
10.16.5
Linking a 4-20mA Input with a 4-
20mA Output
Any analog input from A to N, including phantom
inputs in this range, can be used to control a 4-
20mA output. Use the same steps as above and
choose that input letter.