Configuring Digital Inputs; Configure A Digital Input As A Water Meter - ProMinent Aegis-II Assembly And Operating Instructions Manual

Cooling tower and boiler controller
Hide thumbs Also See for Aegis-II:
Table of Contents

Advertisement

9.10 Configuring Digital Inputs

9.10.1 Configure a Digital Input as a Water
Meter:
NOTE: All digital inputs O-V can be configured for a
pulsing water meter
1- To Enable and Set digital input press MENU
2- Scroll to System and press OK
3- Scroll to Enable I/O and press OK
4- Scroll to select the desired input (O through
V) and press F3
5- Press F3 again to switch from METER to
CONTACT if necessary, then press OK
6- Press MENU
7- Scroll to Water Meter Setup then press OK
8- Scroll down to your meter, then press OK
9- Use F3 to switch to Vol/Contact if
necessary, then use Up/Down and
Left/Right arrow keys to set gallon per
contact or to adjust the K factor, then press
F1 to SAVE.
Note: See
9.2 Naming an Input or Output
rename the relay for example to "Makeup Flow"
Page 59 of 102