Frequency Output Termination; Wiring Sensors To The Controller - ProMinent Aegis-II Assembly And Operating Instructions Manual

Cooling tower and boiler controller
Hide thumbs Also See for Aegis-II:
Table of Contents

Advertisement

Mounting and Installation
6.3.5.7 Connecting a Power Cord
All electrical wiring shall be performed by a licensed electrician,
in accordance with local and national electric codes.
Remove a knock-out from the bottom of the controller and install the cord using a NEMA4/IP66
cord grip as shown in figure 28. See also Figures 9 and 10.
Terminate the line, neutral and ground wires as shown in figure 28. See also figure 22 in the
overview section to open the terminations.

6.3.6 Frequency Output Termination

Outputs 6 through 9 are unpowered digital outputs rated for 24VDC / 250mA which can be
configured as a Pulse or ON/OFF output. See Figure 29.
Figure 29 Digital DC (Pulse) outputs 6-9
6.3.6.1 Using a Universal Control Cable on a Pulse Output Relay
Prominent pumps using the Universal Control cable will terminate using the brown, black and
white wires as shown in Figure 30. This connection is not polarity sensitive. The black is
common. The white is the pulse signal. The brown wire is for pause/enable. When the brown is
not shorted to the black wire, the pump will be in pause mode.

6.3.7 Wiring sensors to the controller

Signal inputs to the controller attach to the main printed circuit board (PCB) or to expansion driver cards. Each input signal is
assigned a letter, A through Z, for program identification. Analog outputs (4-20mA) are assigned an ID of C1 through C8.
Digital outputs are assigned numbers 1 through 9.
In this way, outputs may be programmed to operate based on the status of specified inputs. Relay 3, for example, might be
energized when sensor E reaches a programmed setpoint. Analog outputs (4-20mA) can be programmed to vary
proportionally to an analog input in a forward or reverse direction. Refer to the Aegis Browser manual for programming detail.
6.3.7.1 Inputs on the Main Board
CAUTION!
In pulse mode, these outputs can control the speed of
pulse driven pumps. The frequency outputs vary the
pump speed in much the same manner as a 4-20mA
signal.
In the ON/OFF mode, the outputs will start or stop a pump. The pump frequency
will then be determined manually at the pump.
Poor electrical connection may cause incorrect measurements. Once a
wire is terminated, tug gently on the wire to ensure it is not loose.
Page 34 of 102
Figure 28 Power cord
Figure 30 Universal Control
Cable on Output Relay P6

Advertisement

Table of Contents
loading

Table of Contents