9.11.2 Changing or Unlinking Analog Inputs
Tied to a 4-20mA Output:
Relay outputs are designated by their number, 1
through 9. 4-20mA outputs can be letters C, D, E, F,
I or J. This procedure can be used to change the
input that the mA output represents, or you can
choose 'None'.
Inputs linked to outputs must be un-linked prior to
being disabled.
1- Press MENU
2- Scroll down to I/O Setup and press OK
3- Scroll down to the output letter and press
F2, 'NEXT'.
4- Use the up or down arrows to choose
another input, or choose 'None' and press
OK.
5- Press ESC (Escape).
If unlinking an analog input so as to disable it, return
to the
9.11 Disable an Analog Input,
9.11.3 Changing or Unlinking a Digital Input
Tied to a Digital Output
If a digital input is used as an interlock for a relay, it
must be unlinked prior to being disabled.
1- Press Menu
2- Scroll down to I/O Setup and Press OK
3- Scroll down to the relay or 4-20mA Output
where the interlock is being used. Press OK.
4- Scroll down to Interlock and press OK
5- Press F1 (Remove) to unlink the digital input
from this output.
6- Choose a new interlock or press OK to save
the change. If more than one interlock, use the
arrows to see them and remove as needed.
Escape will void all changes.
See also
10.8 Interlocks
Return to
9.11 Disable an Analog or Digital Input
to finish
to finish.