Programming the Outputs
Rather than a percentage, a pulse relay will show
X milliliters per minute.
10.6.4 Feed Based on Percent Time & Base
Feed
This method applies to the first 5 relays and the
pulse relays when programmed for ON/OFF mode.
The Percent Time program is based on a 5 minute
time frame. The controller calculates the percent of
300 seconds and will turn on the feed relay for that
calculated time. Each 5 minutes, the calculated time
is again applied to the feed relay.
If you have not enabled the Feed relay, see section
10.6 Configuring a Feed Relay.
1- Press MENU
2- Scroll down to Set Feed Mode and press OK.
3- Scroll down to your feed relay and press OK.
4- Scroll down to
Percent Time
5- Use the arrows to edit the percentage and press
OK to save and exit.
A pulse relay in frequency mode also has a base
feed option
and press OK.
Page 70 of 102
Choose Base Feed and enter the milliliters per
minute rate. This pump will then feed constantly
at that rate.
10.6.5 Feed Based on a Sensor with Event
Control
Relays in Feed mode can have an Event Control
whereby the relay will control based on a sensor but
only during the event time.
10.6.6 Set up a relay using the Feed mode with
an oxidant sensor; ORP or any 4-20mA
input.
Use section
10.6 Configuring a Feed Relay
use
10.7 Configuring an Event-Other Relay
event portion.

10.6.7 Choosing a Cycle

1- Press MENU. Scroll down to Biotiming, Events
and press OK
2- Scroll down until you see your relay and press
OK. If you do not see your relay, it is not
enabled. See
10.3 Enable and Configure a
Relay
3- If you do not have any events, you can choose
to add an event or configure the relay. Press F3
to configure the relay.
CONFIG
4- The configure menu allows you to set up a
Prebleed, a Lockout and the Cycle. Scroll down
to Event Cycle and press F1 to
will cover Prebleed and Lockout in the next
section;
10.7.1 Schedules, Prebleeding,
Lockout and With a Sensor
5- Use the right and left arrows to pick Daily,
Weekly or 28 day cycles. Press F1 to
These menus are the same for Pulse relay
event configuration.
then
for the
. We
SELECT
.
Select

Advertisement

Table of Contents
loading