Diagnostics - ProMinent Aegis-II Assembly And Operating Instructions Manual

Cooling tower and boiler controller
Hide thumbs Also See for Aegis-II:
Table of Contents

Advertisement

System Menu
Activity log steps

11.7 Diagnostics

Serial #: serial # of the controller
Fan Speed: displays fan speed, Monitoring fan if it
fails will go to alarm
O-V wiring: 3 Wire meters only and if Digital input
power supply fails because of miss-wiring.
Note: Digital input O-T share a different power
supply than U and V.
Admin Password: Shows Default if it has not been
modified from 'AAAA'. If modified, it will display
'Changed'.
Watchdog Reset: A Watchdog Reset should
always display 0. An increasing number of Resets
indicates corrupted firmware or controller electrical
fault or interference.
Relay Fuse: Displays the state of the Relay 1 and
Relay 2 AC power fuse, Displays "Load Fuse open"
if AC fuse is failed. The Board Fuse does not have
an alarm. If it fails, the controller is without power.
Home Inputs: You can adjust which I/O points are
displayed on the default menu.
See section 2.2 How to Modify the Display's 'Home'
Screen.
HMI Firmware: Hood Firmware Version indicates
the date of issue of the firmware operating the
keypad and display (16.04.06.00 means 2016-April-
6th)
Firmware: Mother board Firmware Version
indicates the date of issue of the firmware operating
the controller (16.08.01.00 means 2016-August-1st)
Page 92 of 102

Advertisement

Table of Contents
loading

Table of Contents