Allen-Bradley ControlLogix System 1756-L1 User Manual page 86

Hide thumbs Also See for ControlLogix System 1756-L1:
Table of Contents

Advertisement

5-10
Communicate with Another Controller over an EtherNet/IP Network
Publication 1756-UM001E-EN-P - August 2002
F.
G.
F. Initially, do you want the module to communicate with the
controller?
If:
Yes
No
EXAMPLE
G. If communication fails, how do you want the controller to
respond?
ATTENTION
!
If you want the
controller to:
fault (major fault)
continue operating
H. Click Finish.
Then:
Leave the check box cleared (unchecked).
Select the check box.
Inhibit a module
To make it easier to test a system one module
or section at a time:
1. Initially, inhibit all the modules.
2. To test a section of the system, clear the
check boxes for the modules of that section
(i.e., uninhibit the modules).
If communication with a modules fails, the
controller operates on old data from the
module. To avoid potential injury or damage,
either monitor communications with modules
or configure modules to produce a major fault
if communications fail.
Then:
Select the check box.
Leave the check box
cleared (unchecked).
42398
Notes:
Monitor the connection
using ladder logic.