18-4
Route PLC-5
or SLC 500
Step:
C. Display the routing table.
D. Define the link ID of the backplane
in which the 1756-DHRIO module
resides.
E. Define the link IDs of the
1756-DHRIO module.
F. Add the remaining communication
module (s) that are in the backplane
(chassis).
Publication 1756-UM001E-EN-P - August 2002
Messages From a DH+
Network
Detailed actions:
1. Start RSLinx software.
To expand a network one level, do one of
the following:
• Double-click the network.
• Select the network and press the
key.
• Click the + sign.
2. Expand the network from step B. until you see the 1756-DHRIO module.
3. Right-click the DHRIO module and choose Module Configuration.
4. Click the DHRIO Routing Table tab.
1. At the top of the routing table, right-click the backplane link and choose
Edit Module ...
2. Type the link ID of the backplane and choose OK.
1. Right-click the 1756-DHRIO module and choose Edit Module ...
2. For each channel, type the link ID of the corresponding network.
3. Choose OK.
1. Right-click the backplane and choose Add Module ...
2. Select the type of device and choose OK.
3. Type or select the slot number of the module.
4. Type the link ID(s) of the network(s) to which the module is connected.
5. Choose OK.
Workstation
+
Linx Gateways, Ethernet
+
AB_DF1-x, DF1
Workstation
+
Linx Gateways, Ethernet
AB_DF1-x, DF1
xx, 1756-Lx
Backplane, 1756-Ax
+
xx, 1756-DHRIO