3-6
Communicate with 1756 I/O over an EtherNet/IP Network
If:
all information must match:
• type
• catalog number
• vendor
• major and minor revision number
all information except the minor revision number Compatible Module
no information must match
Publication 1756-UM001E-EN-P - August 2002
G. How closely must any module in this slot match the information
on this tab?
Then select:
Exact Match
Disable Keying
H. Type the IP address or host name of the module:
To specify an:
Do this:
IP address
host name
Type the host name
I. Click Next.
G.
Notes:
If you select Compatible Module, you can still
replace a 1756-ENET/B module with a 1756-ENBT
module. However, you cannot replace an ENBT
module with an ENET/B module.
1. Select the IP Address button.
2. Type the IP address
H.
42580
Example:
130.151.136.164
aurora6