D. Install a new 1756-BA1 battery.
Only install a 1756-BA1 battery. If you install a
ATTENTION
different battery, you may damage the
!
controller.
E. On the front of the controller, is the BAT LED off?
If:
Then:
Yes
Go the next step.
No
1. Check that the battery is correctly connected to the
controller.
2. If the BAT LED remains on, install another 1756-BA1 battery.
3. If the BAT LED remains on after you complete Step 2.,
contact your Rockwell Automation representative or local
distributor.
41025
F. Attach the battery label:
1. Write on the battery label the date you install the battery.
2. Attach the label to the inside of the controller door.
G. Dispose the old battery according to state and local regulations.
Do not incinerate or dispose lithium batteries
ATTENTION
in general trash collection. They may explode
!
or rupture violently. Follow state and local
regulations for disposal of these materials. You
are legally responsible for hazards created
while your battery is being disposed.