Allen-Bradley ControlLogix System 1756-L1 User Manual page 354

Hide thumbs Also See for ControlLogix System 1756-L1:
Table of Contents

Advertisement

22-4
Configure DF1 Master and Slave Communications
Publication 1756-UM001E-EN-P - August 2002
C. Right-click Controller name_of_controller and select
Properties.
D. Click the Serial Port tab.
E.
F.
G.
H.
I.
J.
E. Select System (default).
F. Select the settings for your DF1 network.
G. Select Half Duplex.
H. Clear (uncheck) the Continuous Carrier check box (default).
I. Type the amount of delay (20 ms units) between the time that
the RTS signal turns on (high) and the time that data is sent. For
example, a value of 4 produces an 80 ms delay.
J. Type the amount of delay (20 ms units) between the time that
the last character is sent and the time that the RTS signal turns
off (low).
42376
42251

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents