Allen-Bradley ControlLogix System 1756-L1 User Manual page 405

Hide thumbs Also See for ControlLogix System 1756-L1:
Table of Contents

Advertisement

If the BAT LED turns on when you apply power to the controller, the battery life may be
IMPORTANT
less then the table below indicates. Some of the battery life may have been used up
while the controller was off and unable to turn on the BAT LED.
Table 25.A Worst-case estimates of battery life
Controller:
Temperature:
1756-L1
60° C
25° C
0° C
1756-L1M1
60° C
25° C
0° C
1756-L1M2
60° C
25° C
0° C
1756-L1M3
60° C
25° C
0° C
1756-L55M12
60° C
1756-L55M13
25° C
0° C
1756-L55M14
60° C
25° C
0° C
1756-L55M16
60° C
25° C
0° C
1756-L55M22
Use the values for the 1756-L55M13 controller.
1756-L55M23
1756-L55M24
Use the values for the 1756-L55M14 controller.
1756-L63
60° C
25° C
0° C
Allen-Bradley HMIs
Time before BAT LED turns on:
Power off 100%
Power off 50%
8 months
8 months
18.5 months
30.5 months
20.2 months
33.7 months
5.6 months
8 months
13.6 months
22.9 months
16.8 months
27.9 months
4 months
7.4 months
11.7 months
20.1 months
16.0 months
26.6 months
2.6 months
4.9 months
9.1 months
16.2 months
14.4 months
24.4 months
57 days
110 days
63 days
123 days
60 days
118 days
29 days
57 days
30 days
61 days
24 days
48 days
15 days
30 days
13 days
27 days
6 days
12 days
22 days
43 days
21 days
42 days
14 days
28 days
Maintain the 1756-BA1 Battery
Time after BAT LED turns on
and then power off 100%:
Yearly
decrease:
24%
16 days
16%
28 days
16%
31 days
24%
8 days
16%
20 days
16%
25 days
24%
6 days
16%
18 days
16%
24 days
24%
4 days
16%
14 days
16%
22 days
23%
69 hours
17%
76 hours
17%
73 hours
23%
35 hours
17%
37 hours
17%
30 hours
23%
18 hours
17%
16 hours
36%
7 hours
23%
6 hours
17%
28 hours
17%
2.5 days
Publication 1756-UM001E-EN-P - August 2002