Allen-Bradley ControlLogix System 1756-L1 User Manual page 71

Hide thumbs Also See for ControlLogix System 1756-L1:
Table of Contents

Advertisement

If this module is a:
digital input
digital input/output
digital output
analog
Allen-Bradley HMIs
6. Select a Comm Format:
IMPORTANT
And the:
Comm Format of the AEN is
Rack Optimization
Comm Format of the AEN is
None
Comm Format of the AEN is
Rack Optimization
Comm Format of the AEN is
None
Comm Format of the AEN is
Rack Optimization
Comm Format of the AEN is
None
7. How closely must any module in this slot match the information
on this tab?
If this information must match:
all, including minor revision number
all except the minor revision number
none
8. Click Next.
Communicate with 1794 I/O Over an EtherNet/IP Network
If the module is also in the I/O configuration of
another controller, then select the Listen Only version
of the Comm Format (e.g., Listen Only - Input Data).
And the module must:
update at the RPI of the AEN
update faster than the RPI of the
AEN
update at the RPI of the AEN
update faster than the RPI of the
AEN
update at the RPI of the AEN
update faster than the RPI of the
AEN
Then select
Exact Match
Compatible Module
Disable Keying
Publication 1756-UM001E-EN-P - August 2002
Then select:
Rack Optimization
Input Data
Input Data
Rack Optimization
Data
Data
Rack Optimization
Output Data
Output Data
Data
4-9