Configure DF1 Master and Slave Communications
Table 22.C Message to a SLC 500 controller
If the data is:
And you want to:
integer (s)
read (receive) data
write (send) data
floating-point (REAL)
read (receive) data
write (send) data
Publication 1756-UM001E-EN-P - August 2002
For this item:
Type or select:
Message Type
SLC Typed Read
Source Element
data table address in the SLC 500 controller (e.g., N7:10)
Number Of Elements
number of integers to transfer
Destination Tag
first element of int_buffer
Message Type
SLC Typed Write
Source Tag
first element of int_buffer
Number Of Elements
number of integers to transfer
Destination Element
data table address in the SLC 500 controller (e.g., N7:10)
Message Type
SLC Typed Read
Source Element
data table address in the SLC 500 controller (e.g., F8:0)
Number Of Elements
number of values to transfer
Destination Tag
first element of the tag (controller-scoped) in this controller
for the data
Message Type
SLC Typed Write
Source Tag
first element of the tag (controller-scoped) in this controller
that contains the data
Number Of Elements
number of values to transfer
Destination Element
data table address in the SLC 500 controller (e.g., F8:0)
C. Click the Communication tab.
D. In the Path box, type the following path:
2, station_address
where:
station_address is the DF1 address of the controller that is
receiving the message.
E. Leave the communication method at the default settings of:
• CIP
• Cache Connections (This check box does not apply to
messages from the serial port.)
F. Click OK.