Programmable Input 1-4 (Active When Connect Gnd (B-) - Smartgen HGM400N Series User Manual

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

7.3 PROGRAMMABLE INPUT 1-4 (ACTIVE WHEN CONNECT GND (B-)

No
Items
0
Not Used
1
High Temp. Input
2
Low OP Warning Input
3
Auxiliary Warning
4
Emergency Stop Input
5
High Temp. Stop Input
6
Generator Closed Input
7
Mains Closed Input
8
Inhibit High Temp. Stop
9
Inhibit Low OP Stop
10
Remote Start Input
11
Low Fuel Level Warn
12
Low Water Level Warn
13
Low Fuel Level Shutdown
14
Low Water Level Shutdown
15
Auto Start Inhibit
16
Remote Control Input
17
Failed To Charge
18
Panel Lock
19
Manual/Auto Switch
20
Alarm Mute
21~31 Reversed
HGM400N Series Genset Controller
HGM400N Series Genset Controller User Manual
If these signals are active after safety on delay, shutdown alarm will
be immediately initiated.
Only warning and not stops if this input is active.
Shutdown alarm will be immediately initiated if this input is active.
When the gen-set is running normally and this signal is activated, if
there is a high temperature situation, the controller will first cool down
the generator and then stop it; if the signal is deactivated and a high
temperature situation occurs, the controller will shut down the
gen-set without cooling down.
Connect to auxiliary port of gen load breaker.
Connect to auxiliary port of mains load breaker.
When it is active, prohibit stopping when high temperature occurs.
Note 2
When it is active, prohibit stopping when low oil pressure occurs.
Note 3
In Auto mode, when input active, genset can be started and with
load after genset is OK; when input inactive, genset will stop
automatically.
Connected to sensor digital input. The controller sends an warning
alarm signal when active.
Connected to sensor digital input. The controller sends an shutdown
alarm signal when active.
In Auto mode, if this input is active, whether mains is normal or not,
the controller will not give a start command to the generator. If
generator is normal running, stop command won't be executed. When
this input is deactivated, genset will automatically start or stop
according to the mains status (normal or abnormal).
All buttons in panel is inactive except
is displayed on LCD. Remote module can switch module mode and
start/stop operation via panel buttons.
Connect to failed to charge output.
All buttons in panel is inactive except
the left of fifth row in LCD when input is active.
When input is active, enter into auto mode automatically, panel
buttons and local operation are inactive; When input is inactive, enter
into manual mode automatically, remote operation is inhibited.
Can prohibit "Audible Alarm" output when input is active.
2017-04-21
Description
and Remote Mode
Version 1.2
and there is
in
Page 26 of 36