Overview; Performance And Characteristics - Smartgen HGM400N Series User Manual

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

1

OVERVIEW

HGM400N series genset controllers integrate digitization, intelligentization and network technology
which are used for genset automation and monitor control system of single unit to achieve automatic
start/stop, data measurement, alarm protection and "three remote" (remote control, remote measuring
and remote communication; SG485 module must be fitted). It fit with LCD display, optional languages
interface (Chinese, English, Spanish, Turkish, Russian and French), and it is reliable and easy to use.
HGM400N series genset controllers adopt micro-processor technology with precision parameters
measuring, fixed value adjustment, time setting and set value adjusting and etc. All parameters can be
configured from front panel or through USB interface by using PC. It can be widely used in all types of
automatic genset control system with compact structure, advanced circuits, simple connections and high
reliability.
2

PERFORMANCE AND CHARACTERISTICS

HGM400N series controller has two types:
HGM410N: ASM (Automatic Start Module),it controls generator to start/stop by remote signal;
HGM420N: AMF (Auto Mains Failure), updates based on HGM410N, moreover, has mains electric
quantity monitoring and mains/generator automatic transfer control function, especially for automatic
system composed by generator and mains.
 132x64 LCD with backlight, selectable language interface (Chinese, English, Spanish, Turkish,
Russian and French), push-button operation;
 Improved LCD wear-resistance and scratch resistance due to hard screen acrylic;
 Silicon panel and pushbuttons for better operation in high/low temperature environment;
 Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems with
voltage 120/240V and frequency 50/60Hz;
 Collects and shows 3-phase voltage, current, power parameter and frequency of generator or mains.
Mains
Line Voltage (Uab, Ubc, Uca)
Phase Voltage (Ua, Ub, Uc)
Frequency (HZ)
Phase Sequence
Load
Current (IA, IB, IC)
Split-phase and Total Active Power (kW)
Reactive Power (kvar)
Apparent Power (kVA)
Power Factor (PF)
Accumulated Energy (kWh)
Output Percentage with Load (
 For Mains, controller has over voltage, under voltage and loss of phase detection functions; For
generator, controller has over voltage, under voltage, over frequency, under frequency, over current
HGM400N Series Genset Controller
HGM400N Series Genset Controller User Manual
Generator
Line Voltage (Uab, Ubc, Uca)
Phase Voltage (Ua, Ub, Uc)
Frequency (HZ)
Phase Sequence
%)
2017-04-21
Version 1.2
Page 4 of 36