Smartgen HGM400N Series User Manual page 20

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

No
Items
30
Low Fuel Level
31
Aux. Sensor
32
Loss of Speed Signal
33
Charge Alt Failure
34
Battery Over Volt
35
Battery Under Volt
36
Current Trans.
Full
Load
Current
37
Rating
Over
Current
38
Percentage
39
Over Current Delay
40
Fuel Pump On
41
Fuel Pump Off
42
Aux. Output 1
43
Aux. Output 2
HGM400N Series Genset Controller
HGM400N Series Genset Controller User Manual
Range
Default
(0-100)%
10
(80-140)ºC
(0-400)kPa
98
(0-100)%
(0-20.0)s
5.0
(0-30)V
6.0
(12-40)V
33.0
(4-30)V
8.0
(5-6000)/5
500
(5-6000)A
500
(50-130)%
120
(0-3600)s
30
(0-100)%
25
(0-100)%
80
(0-17)
14
(0-17)
2
2017-04-21
Description
has expired. If the set value is 0, low oil
pressure signal will not be sent (this only
concerns pressure sensor and does not
concern low oil pressure warning signal via
configurable input port)
When the liquid level of the external sensor falls
below the set value, "Low Fuel Level" timer is
initiated. (this only concerns fuel level sensor
and does not concern low fuel level warning
signal via configurable input port)
Each
value
correspond
(Temperature sensor), 29 (Oil pressure sensor)
and 30 (Level sensor), respectively.
If the set value is 0, only warning and not to
shutdown the generator.
During generator is normal running, when
alternator D+(WL) voltage has fallen below the
set value and remains for 5s, It will initiate a
shutdown alarm signal.
When battery voltage has exceeds the set
value and remains for 20s, It will initiate a
warning alarm signal. Only warning and not to
shutdown the generator.
When battery voltage has fallen below the set
value and remains for 20s, It will initiate a
warning alarm signal. Only warning and not to
shutdown the generator.
The ratio of external CT
Generator's rated current, used for load over
current calculating.
When the load current has exceeded the set
value, "over current" delay is initiated.
When load current has exceeded the set value
and the "over current" delay has expired, over
current alarm is initiated. When the set value is
0, only warning and not to shutdown the
generator.
When fuel level has fallen below the set value
for 10s, "Fuel Pump On" alarm is initiated.
When fuel level has exceeded the set value for
10s, "Fuel Pump Off" alarm is initiated.
Factory default: Fuel Relay Output
Factory default: Energized To Stop