Smartgen HGM400N Series User Manual page 22

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

No
Items
70
AC System
71
Temp. Sensor Curve
72
Pressure Sensor Curve
73
Multiplex Input 1
74
Level Sensor Curve
75
Multiplex Input 2
76
Config. Sensor Curve
77
Poles
78
Temp. Sensor Open
79
OP Sensor Open
Fuel
Level
80
Open
81
Config. Sensor Open
82
Cooling Blower On
83
Cooling Blower Off
84
Low Fuel Level Warn
85
Gen Over Volt Warn
86
Gen Under Volt
87
Gen Over Freq Warn
88
Gen Under Freq Warn
89
Gen Over Current Warn
HGM400N Series Genset Controller
Range
(0-3)
(0-12)
(0-12)
(0-1)
(0-7)
(0-3)
(0-9)
(0-9)
(0-5)
(2-64)
(0-2)
(0-2)
Sensor
(0-2)
(0-2)
(0-140)℃
(0-140)℃
(0-100)%
(30-620)V
(30-620)V
(0-75.0)Hz
(0-75.0)Hz
(50-130)%
HGM400N Series Genset Controller User Manual
Default
0: 3P4W; 1: 2P3W
0
2: 1P2W; 3: 3P3W
8
SGX See
7.4
8
SGX See
7.4
0: Digital Input 3
0
1: Level Sensor
3
SGD See
7.4
0: Digital Input 4
1: Temperature Sensor
0
2: Oil Pressure Sensor
3: Level Sensor
8
SGX
8
SGX
3
SGD
4
0:Indication; 1:Warn; 2:Shutdown
1
(temperature sensor will show "+++");
0: Indication (oil pressure sensor will show
"+++");
1
1:Warn; 2:Shutdown
0: Indication (fuel level sensor will show "+++");
1
1:Warn; 2:Shutdown
0: Indication (LCD display will show "+++");
1
1:Warn; 2:Shutdown
60
It controls the cooling blower to open or close if
the output port is configured as Cooling Blower.
40
When the liquid level of the external sensor falls
below the set value, "Low Fuel Level" timer is
20
initiated. (this only concerns fuel level sensor
and does not concern low fuel level warning
signal via configurable input port)
When genset voltage is over the point,
253
generator over voltage is active. When the point
is 620V, generator over voltage is disabled.
When generator voltage is under the point,
generator under voltage is active. When the
193
point is 30V, generator under voltage is
disabled.
When generator's frequency is over the point,
55.0
generator over frequency is active.
When generator frequency is lower than the
42.0
point, warn alarm signal will be sent.
110
When load current is over the point, over
2017-04-21
Version 1.2
Description
Note 5
Page 22 of 36