7.3 PROGRAMMABLE INPUT 1-4 TABLE

Table 13 - Definition Content of Programmable Input 1-4 (Active When Connect To Ground (B-)
No.
Items
0
Not Used
1
High Temperature Shutdown
2
Low Oil Pressure Shutdown
3
External Warn Input
4
External Shutdown Input
5
WTH Cooling Stop
6
Generator Closed Auxiliary
7
Reserved
8
Inhibit WTH Stop
9
Inhibit OPL STOP
10
Remote Start
11
Low Fuel Level Warning
12
Low Coolant Level Warning
13
Low Fuel Level Shutdown
14
Low Coolant Level Shutdown
15
Inhibit Start Auto
HGMS61 Genset Controller User Manual
This function only suits for HGMS61 CAN with engine type
Yuchai-LMB. When unit is standby, pump control will output per 30
minutes. If oil pressure is above 100kPa or output delay is more
than 1minute, it will stop output; if unit is in pre-heating state, oil
pump control will always output.
If output port is set this function, when genset status enters fuel,
the fuel will output when pre-supplied fuel output for 3s, otherwise,
the fuel will output immediately.
ECU key switch will output when fuel output delays for 3s. When
fuel disconnects, it will disconnect output immediately.
If the signal is active after safety run on delay is over, the
genset will immediately alarm to shutdown.
Only warning, not shutdown.
If the signal is active, genset will immediately alarm to
shutdown.
During engine running and the input is active, if high
temperature occurs, controller will stop after high speed
cooling; when the input is disabled, controller will stop
immediately.
Connect to auxiliary port of gen load breaker.
When it is active, high oil temperature stop is inhibited. See
Note2 of Parameter Configuration for more information.
When it is active, low oil pressure stop is inhibited. See Note3
of Parameter Configuration for more information.
In Auto mode, when input active, genset can be started and
with load after genset is OK; when input inactive, genset will
stop automatically.
Connect to sensor digital input. The controller will send a
warning alarm signal when input is active.
Connect to sensor digital input. The controller will send a
shutdown alarm signal when input active.
In Auto Mode, when the input is active, no matter mains
normal or not, genset won't start. If genset is in normal
running, stop process won't be executed. When input is
disabled, genset will automatically start or stop judging by
Description
Description
Page 28 of 47