Pin
Function
11
Engine Temp. Sensor
12
Oil Press Sensor
13
Current IA
14
Current IB
15
Current IC
16
Current COM
17
Magnetic Pickup
18
Charger D+
19
Aux. Output 4
20
Aux. Output 5
21
Aux. Output COM
22
Gen AC Voltage U
23
Gen AC Voltage V
24
Gen AC Voltage W
25
Gen AC Voltage N2
26
Mains AC Voltage R
27
Mains AC Voltage S
28
Mains AC Voltage T
29
Mains AC Voltage N1
Note: USB interface is parameters programmable interface that can be programmed via PC.
HGM400N Series Genset Controller
HGM400N Series Genset Controller User Manual
Cable Size
Connect to temperature/cylinder
2
1.0mm
resistance sensor.
Connect
2
1.0mm
resistance sensor.
Outside connected to secondary coil of current
2
1.5mm
transformer(rated 5A)
Outside connected to secondary coil of current
2
1.5mm
transformer(rated 5A)
Outside connected to secondary coil of current
2
1.5mm
transformer(rated 5A)
2
1.5mm
See INSTALLATION in this manual.
Connect to speed sensor;
2
0.5mm
Shielded wire is recommended.
The other end of speed sensor connects to B-.
Connect to charging starter's D+ terminal. If there is
2
1.0mm
no this terminal, then be hang up.
The combination of terminal 19 and 21 is relay
2
1.0mm
normally open contact; rated 5A; Voltage free.
The combination of terminal 20 and 21 is relay
2
1.0mm
normally open contact; rated 5A; Voltage free.
2
1.5mm
Common terminal of auxiliary output 4 and 5.
Connected to U-phase of generator (2A fuse is
2
1.0mm
recommended)
Connected to V-phase of generator (2A fuse is
2
1.0mm
recommended)
Connected to W-phase of generator (2A fuse is
2
1.0mm
recommended)
2
1.0mm
Connected to N-wire of generator.
Connected to R-phase of mains (2A fuse is
2
1.0mm
recommended) (HGM410N without)
Connected to S-phase of mains (2A fuse is
2
1.0mm
recommended) (HGM410N without)
Connected to T-phase of mains (2A fuse is
2
1.0mm
recommended) (HGM410N without)
2
1.0mm
Connected to N-wire of mains (HGM410N without)
2017-04-21
Description
to
oil
pressure
Version 1.2
See
7.4
Page 17 of 36