Smartgen HGM400N Series User Manual page 21

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

No
Items
44
Aux. Output 3
45
Aux. Output 4
46
Aux. Output 5
47
Digital Input 1
48
Digital Input 1 Active
49
Digital Input 1 Delay
50
Digital Input 2
51
Digital Input 2 Active
52
Digital Input 2 Delay
53
Digital Input 3
54
Digital Input 3 Active
55
Digital Input 3 Delay
56
Digital Input 4
57
Digital Input 4 Active
58
Digital Input 4 Delay
59
Power On Mode
60
Module Address
61
Passwords
62
Crank Disconnect
Disconnect
Magnetic
63
Pickup
64
Disconnect Gen Freq
65
Disconnect OP
High
Temp.
66
Enabled
67
Low OP Inhibit Enabled
68
Low Fuel Level Inhibit
69
Config. Sensor Inhibit
HGM400N Series Genset Controller
Range
(0-17)
(0-17)
(0-17)
(0-15)
(0-1)
(0-20.0)s
(0-15)
(0-1)
(0-20.0)s
(0-15)
(0-1)
(0-20.0)s
(0-15)
(0-1)
(0-20.0)s
(0-2)
(1-254)
(0-9999)
(0-6)
(0-3000)r/min
(10.0-30.0)Hz
(0-400)kPa
Inhibit
(0-1)
(0-1)
(0-1)
(0-1)
HGM400N Series Genset Controller User Manual
Default
3
Factory default: Idle Control
5
Factory default: Close Generator
6
Factory default: Mains Closed
1
Factory default: High Temperature Input
0
Factory default: Close to active
2.0
Factory default: Low Oil Pressure Warning
2
Input
0
Factory default: Close to active
2.0
10
Factory default: Remote Start
0
Factory default: Close to active
2.0
11
Factory default: Fuel Level Warn
0
Factory default: Close to active
2.0
0: Stop Mode
0
1: Manual Mode
2: Auto Mode
1
Communication address of controller.
0318
There are 3 conditions of disconnecting starter
with engine: Generator Frequency, Magnetic
Pickup, Oil Pressure. Each condition can be
2
used alone and simultaneously to separating
the start motor and genset as soon as possible.
See
7.5
When engine speed higher than the set value,
360
starter will be disconnected.
When generator frequency higher than the set
14.0
value, starter will be disconnected.
When generator oil pressure higher than the set
200
value, starter will be disconnected.
Factory default: when high temperature occurs,
0
shutdown alarm is initiated. Note 2
Factory default: when low oil pressure occurs,
0
shutdown alarm is initiated. Note 3
Factory default: when low fuel level occurs,
1
shutdown alarm is initiated. Note 4
Factory default: when config. sensor value
higher/lower than the set value (particular case
1
depends on the sensor type), shutdown alarm
is initiated.
2017-04-21
Version 1.2
Description