Definition Of Relay Outputs (Table 2); Definition Of Digital Inputs (Active When Connect To Gnd (B-)); (Table 3) - Smartgen HGM1780 User Manual

Automatic genset controller
Table of Contents

Advertisement

6.2 DEFINITION OF RELAY OUTPUTS (TABLE 2)

No.
Items
0
Not used
Common
1
Alarm
Energized to
2
Stop
3
Idle control
Preheat
4
control
Closing
5
Gens
6
Reserved
6.3 DEFINITION OF DIGITAL INPUTS (ACTIVE WHEN CONNECT TO
GND (B-)) (TABLE 3)
Description
No.
0
Not Used
High
1
Input
Low
2
Input
3
Reserved
4
Auxiliary Shutdown
Digital
Inputs
High
5
Stop Input
6
Reserved
7
Reserved
8
Fuel Level Sensor
HGM1780
Automatic
HGM1780 Automatic Genset Controller
Output is not active.
Includes all shutdown alarms and warning alarms. Warning
alarms are not self-latching, while shutdown alarms are and will
not disappear until they are reset.
Suitable for the genset with stop electromagnet. The
electromagnet closes when stop idle is over. And opens when
EST delay is over.
Used for machines that have idle mode. Closes during
cranking, disconnects during warming up, closes during stop
idle delay, disconnects after complete stop.
It closes before starting and opens before starter is power on.
During normal operation of the generator, closes the breaker
Temperature
OP
Warning
Temperature
Genset Controller
ISSUE 2013-04-03
Description
If these signals are activated after crank
disconnect,
shutdown
immediately initiated.
Only warning and not stops if this input is
active.
Shutdown
alarm
initiated if this input is active.
When the gen-set is working normally and
this signal is activated, if there is a high
temperature situation, the controller will first
cool down the generator and then stop it; if
the signal is deactivated and a high
temperature situation occurs, the controller
will shut down the gen-set without cooling
down.
See Table 4.
Version1.7
Notes
alarm
will
will
be
immediately
Page 17 of 24