Sensor Setting - Smartgen HGM400N Series User Manual

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

setting interface.
9

SENSOR SETTING

1) When reselect sensors, the sensor curve will be transferred into the standard value. For example, if
temperature sensor is SGH (120°C resistor type), its sensor curve is SGH (120°C resistor type); if
select the SGD (120°C resistor type), the temperature sensor curve is SGD curve.
2) If there is difference between standard sensor curve and chosen sensor curve, select "defined
sensor", and then input defined sensor curve.
3) When input the sensor curve, X value (resistor) must be input from small to large, otherwise,
mistake occurs.
4) If there is no oil pressure sensor, but there is low oil pressure alarm switch, user must set the oil
pressure sensor as "None", otherwise, maybe low oil pressure shutdown occurs.
5) The headmost or backmost values in the vertical coordinates can be set as same as below,
1Pa
2
1kgf/cm
1bar
1psi
HGM400N Series Genset Controller
Common unit conversion table
2
N/m
Pa
1
4
9.8x10
5
1x10
3
6.89x10
HGM400N Series Genset Controller User Manual
2
kgf/cm
5
1.02x10
1
1.02
2
7.03x10
2017-04-21
Version 1.2
bar
5
1x10
1.45x10
0.98
14.2
1
14.5
2
6.89x10
Page 30 of 36
psi
4
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hgm420nHgm410n

Table of Contents