90
High Temp. Warn
91
Low OP Warn
92
Aux. Sensor Warn
93
Gen Over Volt Delay
94
Gen Over Freq Delay
95
Disconnect OP Delay
96
Timing Start
97
Timing Start Circulate
98
Auto Start Inhibited
Auto
Start
Circulate
99
Inhibited
HGM400N Series Genset Controller
HGM400N Series Genset Controller User Manual
Range
Default
(80-140)℃
95
(0-400)kPa
124
(80-140)ºC
(0-400)kPa
95
(0-100)%
(0-20.0)s
10.0
(0-20.0)s
2.0
(0-20.0)s
0.0s
(0-1)
0
(0-1)
0
(0-2)
0
(1-31)
1
(0-7)
0
(1-23)h
0
(1-59)min
0
(0-30000)min
30
(0-1)
0
(0-2)
0
(1-31)
1
2017-04-21
Description
current is active. When this value is 0, warn
alarm signal won't be sent.
When the temperature value of the external
temperature sensor exceeds the set value,
"High Temperature" timer is initiated. Detecting
only after safety on delay has expired. If the set
value is 140, high temperature signal will not be
sent (this only concerns external temperature
sensor, not high temperature signal via config.
input port).
When the external pressure sensor value falls
below this set value, "Low Oil Pressure" timer is
initiated. Detecting only after safety on delay
has expired. If the set value is 0, low oil
pressure signal will not be sent (this only
concerns pressure sensor and does not
concern low oil pressure warning signal via
configurable input port)
Respective
corresponding
sensor, 91 pressure sensor and 84 level sensor
in this table.
When generate voltage exceeds shutdown
value and last for a while, gen over volt
shutdown is active.
When generate frequence exceeds shutdown
value and last for a while, gen over freq
shutdown is active.
When
disconnect
pressure and engine oil pressure is higher than
disconnect oil pressure delay, the genset is
regarded as start successfully and starter will
disconnect.
0: Disabled; 1:Enabled
0:No-load; 1:On-load
0: monthly; 1: weekly; 2:daily
Day(0:monthly is active)
Week(0:weekly is active)
Prohibit start time (h)
Prohibit start time (min)
Duration
0: Disabled; 1:Enabled
0: monthly; 1: weekly; 2:daily
Day(0:monthly is active)
Version 1.2
with
90
temp.
conditions
include
Page 23 of 36