Defined Contents Of Programmable Input 1-5 - Smartgen HGM6100N Series User Manual

Genset controller
Hide thumbs Also See for HGM6100N Series:
Table of Contents

Advertisement

DEFINED CONTENTS OF PROGRAMMABLE INPUT 1-5

7.3
Table 9 – Defined Contents of Programmable Input 1-5 (All Ground (B-) Connected Active)
No.
Items
0
Not Used
1
High Temperature Shutdown
2
Low Oil Pressure Shutdown
3
Warn Input
4
Shutdown Input
5
WTH STOP by Cool
6
Generator Closed Auxiliary
7
Mains Closed Auxiliary
8
Inhibit WTH STOP
9
Inhibit OPL STOP
10
Remote Start
11
Fuel Level Low Warning
12
Coolant Level Low Warning
13
Fuel Level Low Shutdown
14
Coolant Level Low Shutdown
15
Inhibit Auto Start
16
Remote Control
17
Charge Alt Fail IN
18
Panel Lock
19
Alarm Mute
20
Idle Control Mode
21
60Hz Select
HGM6100N Series Genset Controller User Manual
If the signal is active after safety run delay over, genset will
immediately alarm to shutdown.
Only warning, not shutdown.
If the signal is active, genset will immediately alarm to
shutdown.
During engine running and the input is active, if high
temperature occurs, controller will stop after high speed
cooling; when the input is disabled, controller will stop
immediately.
Connect to auxiliary port of gen load breaker.
Connect to auxiliary port of mains load breaker.
When it is active, high oil temperature stop is inhibited. See
NOTE2 of Table 7 for more information.
When it is active, low oil pressure stop is inhibited. See NOTE3
of Table 7 for more information.
In Auto mode, when input active, genset can start and take
load after genset is OK; when input inactive, genset will stop
automatically.
Connected to sensor digital input. The controller sends an
warning alarm signal when active.
Connected to sensor digital input. The controller sends an
shutdown alarm signal when active.
In Auto Mode, when the input is active, no matter mains normal
or not, genset won't start. If genset is in normal running, stop
process won't be executed. When input is disabled, genset will
automatically start or stop judging by mains normal or not.
All buttons in panel is inactive except
Remote Mode is displayed on LCD. Remote module can switch
module mode and start/stop operation via panel buttons.
Connect to failed to charge output.
All keys in panel are inactive except
is
in the right of fifth row in LCD when input is active.
Can prohibit "Audible Alarm" output when input is active.
In this mode, under voltage, under frequency and under speed
are not protected.
It is used for J1939 engine with CANBUS port, when input is
Description
and
and there
Page 27 of 47