Smartgen HGM400N Series User Manual page 24

Genset controller
Hide thumbs Also See for HGM400N Series:
Table of Contents

Advertisement

No
Items
100 Over Power
101 Date
102 Custom Sensor Curve
Note1: The default value in "No." column is for HGM420N and the number value needs to minus 5 for
HGM410N.
Note2: if "high temperature inhibit" is configured, or set auxiliary input as "inhibit high temperature
stop" and this input is active, when temperature is higher than the preset value, or high temperature
alarm input is active, controller will send warning signal only and not stop the unit.
Note3: if "low oil pressure inhibit" is configured, or set auxiliary input as "inhibit low oil pressure stop"
and this input is active, when oil pressure is lower than the preset value, or low oil pressure alarm input
is active, controller will send warning signal only and not stop the unit.
Note4: if "low fuel level inhibit" is configured, or set auxiliary input as "inhibit low fuel level stop" and
this input is active, when fuel level is lower than the preset value, or low fuel level alarm input is active,
controller will send warning signal only and not stop the unit.
Note5: Multiplex Input can be set as "auxiliary input" or "level sensor"; if one of them is set
successfully, then the corresponding items are active. For instance, if set "Multiplex Input 3" as "Auxiliary
Input", the related configuration items of auxiliary input 3 are active; if set "Multiplex Input 3" as "Level
Sensor", the related configuration items of level sensor are active;
Note6: If default password (0318) isn't changed, it doesn't need to input when configuring
parameters via PC software; if the password is changed for the first time via PC software, it need to input
password in password window.
Note7: Between input correct password and LCD back light haven't got dark, input parameter
numbers can enter parameter setting interface when enters "Password Input" again.
Note8: In teeth configuration interface, configure teeth status and power large than 20Hz, press start
key for auto calculating teeth numbers and press confirm key for changing teeth numbers.
HGM400N Series Genset Controller
HGM400N Series Genset Controller User Manual
Range
Default
(0-7)
0
(1-23)h
0
(1-59)min
0
(0-30000)min
30
(0-2)
0
(0-6000)kW
304
(0-6000)kW
290
(0-3600)s
5
Set the date of controller.
(0-3)
0
2017-04-21
Description
Week(0:weekly is active)
Prohibit start time (h)
Prohibit start time (min)
Duration
0 Inactive; 1 Warn; 2 Alarm Shutdown
Over power setting value
Over power warn return
Over power delay
When power is higher than preset value and
duration exceeds than delay, over power
warning is active. Return and delay value can
be set.
0 Custom temperature sensor
1 Custom pressure sensor
2 Custom level sensor
3 Custom auxiliary sensor
Choose sensor which need to be set, input
every point(8 points need to be input)
resistance and corresponding value(or current,
voltage) of curve.
Version 1.2
Page 24 of 36