6 Start-up
⇒
PARAM
60
To enter the menu, proceed as follows:
CODE
CHOICE
(default = bold)
M1
off
on
M2
Batch one-sided
Inline one-sided
Batch two-sided
Inline two-sided
M3
Actuators
Sensors
Feedback
Curve
Actuators:
With selection "one-sided" in field M1:
MA1
Acid
Alkali
MA2
Pulse length
Pulse-frequency
3-point step controller
Current output
⇒
INFO
!
Selection of Controller settings
Note!
You must activate the controller settings after you have
configured the controller in this menu branch.
Select the process type,
which describes your process.
One-sided: control using either acid or alkali
Two-sided: control using either acid and alkali.
You can only select this function if you have defined two
controllers (in the "Contacts" menu and/or via the cur-
rent output).
Select external hardware
For correct operation, you must completely configure
these four submenus.
Actuators: here, you can select and configure the
methods which the controller uses to output the set
values.
Sensors: here you configure the look-ahead pH measu-
rement or switch channels (only with two-circuit).
Feedback: here you configure the position feedback of
an actuator drive (only with the selection of three PS
and position feedback = on; see Fields 162, 165 / 170,
165)
Curve: here, you enter the controller parameters (neu-
tral zone, set point, etc.). With this selection, you can
also reach the "active measuring menu" (see Field 196).
Dosing
Select the medium to be dosed to the process.
Select control type
Mycom S CPM 153
Endress+Hauser