Analog Output Control

Using the fieldbus for analog output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 55: Analog Output Control Protocol Reference
Drive Parameter
1501
AO1 CONTENT SEL
0135
COMM VALUE 1

PID Control Setpoint Source

Use the following settings to select the fieldbus as the setpoint source for PID loops:
Table 56: PID Control Setpoint Source Protocol Reference
Drive Parameter
SET POINT SEL
4010
(Set 1)
SET POINT SEL
4110
(Set 2)
SET POINT SEL (Ext/
4210
Trim)

Communication Fault

When using fieldbus control, specify the drive's action if serial communication is lost.
Table 57: Communication Fault Reference
Drive Parameter
3018
COMM FAULT FUNC
3019
COMM FAULT TIME
OM 1190-1 • MD4 VFD
Value
135
Analog Output 1 controlled by
(COMM VALUE 1)
writing to parameter 0135 .
Value
Setpoint is either: Input Reference
2 (+/-/* AI1) . Control requires
8 (COMM VALUE 1)
parameter 1106 value = comm .
9 (COMM + AI1)
Process PID setpoint . Control
requires parameter 1106 value =
10 (COMM*AI1)
pid1 out and parameter 4010 value
= comm .
Value
Description
0 (NOT SEL)
1 (FAULT)
Set for appropriate drive response .
2 (CONST SP7)
3 (LAST SPEED)
Set time delay before acting on a communication loss .
Setting
abb drv
Setting
abb drv
78
f
Ieldbus
Protocol Reference
Modbus
N2
dcu profile
40135
AO14
Protocol Reference
Modbus
N2
dcu profile
40003
AO2
www .DaikinApplied .com
C
onTrols
FLN
BACnet
46
AO0
FLN
BACnet
61
AV17