E5 Outdoor Unit: Inverter Compressor Motor Lock - Daikin RXYQ96PYDN Service Manual

R-410a heat pump 60hz, r-410a heat recovery 60hz
Hide thumbs Also See for RXYQ96PYDN:
Table of Contents

Advertisement

SiUS34-801A_b
E5
3.17
Outdoor Unit: Inverter Compressor Motor Lock
E5
Remote
Controller
Display
Applicable
RXYQ72P~240PYDN, PTJU
Models
REYQ72P~240PYDN, PTJU
Method of
Inverter PC board takes the position signal from UVW line connected between the inverter and
Malfunction
compressor, and the malfunction is detected when any abnormality is observed in the
phase-current waveform.
Detection
Malfunction
This malfunction will be output when the inverter compressor motor does not start up even in forced
Decision
startup mode.
Conditions
Supposed
Causes
Troubleshooting
Inverter compressor lock
High differential pressure (72.5psi or more)
Incorrect UVW wiring
Faulty inverter PC board
Stop valve is left in closed.
Troubleshooting by Indication on the Remote Controller